BUS (EIB)

INSTALLATION CABLE

PRESENTATION

This cable is used for BUS (EIB) system applications, transmission of measured values and for being used in automated and adjustment fields.

REFERENCE STANDARDS

According to the example DIN VDE 08 15

CABLE STRUCTURE

1- Conductors :

Conductors consist of a solid annealed copper with a nominal diameter of 0.8 mm.

2- Insulation of conductors :

Conductors are insulated with :
- PVC for EIB J-Y(St)Y cables.
- Halogen free compound for EIB-J-H(St)H

More info

3- Standing :

The insulated wires are assembled in pairs, fours, fives, and sixes according to the customer's requirements.

MECHANICAL CHARACTERISTICS

Elongation at break of conductors: ≥ 15%
Elongation at break of insulation: ≥ 125%

ELECTRICAL CHARACTERISTICS

Maximum Conductor resistance Ø 0,5mm 97,8 ? /km
Test voltage 3,750 KV (1 min)
Minimum Insulation resistance1000M? .km